PCB-682A14
- Transmitter for mounting on a top hat rail
- Connection of an industrial ICP® vibration sensor
- Integrated sensor supply
Specifications | |||
---|---|---|---|
Basic data | English units | SI units | |
Number of channels | 1 | ||
Input signal (vibration) | ±100 mV/g | ±10,2 mV/(m/s²) | [4] |
Output signal (vibration DC) | 4… 20 mA | [3] | |
Output signal (vibration AC) | 100 mV/g | 10,2 mV/(m/s²) | [1] |
Frequency range (-3 dB) (speed) | 210 … 600.000 cpm | 3.5 ... 10k Hz | [2] [5] [6] |
Output range (speed DC) | 0 … 1,00 in/sec pk | 0 … 25,4 mm/s pk | [4] |
Conditions of use | |||
Temperature range (operation) | -13 ... 158 ° F | -25 ... 70 ° C | |
Temperature range (storage) | -40 ... 257 ° F | -40… 125 ° C | |
Humidity (non-condensing) | 0… 95% | ||
Technical characteristics | |||
care | DC voltage | ||
tension | 23… 25 V DC | ||
Current consumption (maximum) | 100 mA | ||
Settling time | <2 min | ||
Supply voltage (for sensor) | 19… 21 V DC | ||
Constant current supply (for sensor) | 3… 5 mA | ||
Output range (± 5.0%) (DC current output vibration) | 16 mA | ||
Physical characteristics | |||
Connection (input / output) | Removable connection terminals | ||
Connection (output for vibration raw signal) | BNC socket | ||
Housing material | polyamide | ||
Size - height | 3.9 in | 99 mm | |
Size - width | 0.9 in | 22.5 mm | |
Size - depth | 4.5 in | 114.5 mm | |
Mass (maximum) | 6,4 oz | 127 grams | |
Connection wire cross-section | 24-14 AWG | ||
Top hat rail | 1.38 in | 35 mm | |
Status display (operation) | Green LED | ||
Status display (error) | Red LED |
Hints | |||
---|---|---|---|
[1] | Based on a sensor sensitivity of 100 mV / g | ||
[2] | Attenuation: -40 dB / decade | ||
[3] | The output signal fluctuates at frequencies below 5 Hz. | ||
[4] | The scaled output signal (U, I) is based on an ICP® sensor signal with a sensitivity of ± 100 mV / G | ||
[5] | Tolerance of the lower limit frequency: ± 0.5 Hz | ||
[6] | Tolerance of the upper limit frequency: ± 1.0 kHz | ||
[7] | Details: see PCB Declaration of Conformance PS124 |