Input | |||
Vibration measurement | ICP® power supply, 4 mA at 20... 30 V Sensitivity 10... 1000 mV / g Resolution 4 mg (at Sensitivit? 100 mV/g) Digital review filter -RMS level: 10... 1,000 Hz in accordance with DIN ISO 10816-1 bzw. 2 … 1.000 Hz, 2.000 Hz, 3.000 Hz, 5.000 Hz (einstellbar) -Transient shock: HP 1,000 Hz, 2,000 Hz, 4,000 Hz, 6,000 Hz (einstellbar) bis?50.000 Hz für Transientenerfassung | ||
Temperature measurement | Voltage input 0... 2 V, sensitivity adjustable Suitable for the connection of vibration sensors with Option "TO" | ||
Process parameters | 0... 20 mA, Signalber. scalable up to 120% | ||
Speed | CW-219-0... 20 mA, Signalber. scalable (300... 12,000 rpm) CW-220: active or passive rotary encoders -Number of pulses: 1... 720 pulse per revolution (adjustable) -Max frequency: 36,000 Hz -Reference pulse 1 x per revolution for position determination | ||
Outputs | |||
Switching relay | 1 x closer, 1 x opener with security control Alarms can be configured Maximum switching voltage 48 V, maximum switching current 1 A | ||
Time signal vibration | Non-valuated analog sensor signal | ||
Interfaces | |||
Configuration and online mode | CAN-bus with USB adapter LAN and Wi-Fi in conjunction with module CW-103 | ||
General information | |||
Supply voltage | 24 V DC nominally, working range 20... 30 V DC | ||
Power consumption | Approx. 80 mA (at 24 V) | ||
Galvanic isolation | Current interface and CAN-bus | ||
Temperature range | -10... 70 ° C | ||
Type of protection | IP20 | ||
Housing | DIN rail housing with screw-type | ||
Dimensions (WxHxD) | 45 x 120 x 120 mm | ||
Additional informations | |||
Input | 1 x ICP®
| ||
Signal evaluation | RMS acceleration
| ||
Monitoring functions | 2 adjustable alarm thresholds
|